Electric Power

Generator Set Specifications

Maximum Rating
9.5 kVA
Minimum Rating
6.8 kVA
Emissions/Fuel Strategy
R96/EUIIIa Equivalent
Voltage
110 to 415 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
C1.1, In-line 4 4-cycle diesel
Bore
3in
Stroke
3.2in
Displacement
69inĀ³
Compression Ratio
23.0:1
Aspiration
Naturally Aspirated
Fuel System
Indirect Injection
Governor Type
Mechanical

Generator Set Dimensions

Length - Maximum
55.1in
Width - Maximum
24.4in
Height - Maximum
39.2in

Standard Equipment:

  • Air Inlet System
    • Air cleaner; light duty with disposable element
  • Control Panel
    • GCCP1.3 control panel
  • Cooling System
    • Coolant drain line with valve
    • Caterpillar extended life coolant
    • Radiator and cooling fan with guards
    • Fan drive, battery charging alternator drive
  • Fuel System
    • Base, formed steel with single wall integral 8-hour fuel tank
    • Standard open set fuel tank / base supplied
  • Exhaust System
    • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use; shipped loose
  • Generators And Generator Attachments
    • Tower panel, IP22, bottom cable entry
    • Circuit breaker, IEC, 3 pole, mounted in tower panel
    • Voltage regulator (single phase sensing)
    • IP23 Protection
    • Segregated low voltage (AC/DC) wiring panel
    • 12 Leads
  • Governing System
    • Mechancial governing system
  • Lube System
    • Lubricating oil
    • Oil drain line with valve
  • Mounting System
    • Captive linear vibration isolators between base and engine-generator
    • Skidbase as standard
    • Anti-vibration mounts
    • Includes lifting provisions and termination points for coolant
  • Starting / Charging System
    • 12 Volt battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment:

  • Alternator Options
    • Coastal insulation protection
  • Certificates
    • European upgrade to STD set for CE certificate
    • Global certification for CIS
  • Circuit Breakers
    • 4 Pole circuit breaker
    • Pad-lockable breaker device
  • Control Panel
    • Volt free contacts for common alarm
    • Emergency stop with key
    • Battery charger
    • GCCP 1.3
  • Control Pane
    • Volt free contacts for genset running
  • Cooling System
    • Coolant heater
  • Enclosures
    • Sound attenuated enclosure (GALV)
    • Single point lift for enclosure
  • Fuel System
    • Low fuel level alarm
  • Mounting Options
    • Silencer installation kit
    • Battery removal
    • Industrial silencer removal
  • Special Test And Inspection
    • PGS test report @1.0 power factor
  • General
    • Packing case - compact set
    • Radiator stone guard
    • Packing case - canopied set